AVR MX321 AVR voltage regulator

Sensing input voltage: 190 -264 V AC max, 2 or 3 phases.
Power supply input (PMG). Voltage: 190-220 V AC max.3 phases, 3 wires.
Power input current: 3A/phase
AVR MX321 Automatic voltage regulator for alternator generator voltage regulator Genset

Categoría: Etiquetas: ,
Consultar al WhatsApp
Loading...

Descripción

Technical specifications

Input detection

voltage: 190 -264V AC max.2 or 3 phases

Frequency: 50-60 Hz nominal

Power supply input (PMG)

Voltage: 190-220V AC max. 3-phase 3-wire

current: 3A/phase

Output

Voltage: max. 120 V DC.

Current: continuous 3.7 A intermittent 6 A for 10 seconds.

Resistance: 15 ohms minimum

regulation: +/- 0.5% RMS with 4% motor regulation

Thermal drift: 0.02% per degree C change in AVR environment

Soft start ramp time: 0.4-4 seconds.

Typical system response

AVR response:10 ms

Archived current at 90%: 80 ms

Machine volts up to 97%: 300 ms

External voltage adjustment: +/- 10% with 5 k ohms 1 W trimmer

Protection under frequency

Set point: 95% Hz (see Note 5)

Slope: 100-300% up to 30 Hz

Max. dwell time: 20% volts/s recovery

Unit power dissipation: 18 watts max.

Analog input

Maximum input +/- 5 V DC

Sensitivity1v for 5% volt generators (adjust)

Input resistance1k ohm

Quadrature input

10 ohm load

Maximum sensitivity: 0.22 A for 5% OPF.

Maximum input: 0.33 A.

Current voltage sensing input

Set point: 300 V. Time delay: 1 second (fixed).

CB coil volts of 10 – 30 VDC

CB Trip Coil Resistance: 20-60 ohms